| Criteria |
Corrective
Action |
| The
substrate is dry, frost free, clean, smooth, firm, and clear of damaging
objects |
Delay
installation of vapor retarder until substrate conditions are corrected. |
| Products are protected
from weather, damage, and abuse by other trades. |
Protect products and remove
damaged products from project site. |
| The location of the vapor
retarder is as specified. |
Remove vapor retarder
from incorrect location and install in specified location. |
| Quantity of vapor retarder
sheets are as specified. |
Install additional vapor
retarder sheets to comply with the specifications. |
| Fields asphalt is applied
as specified. |
Install additional Fields
asphalt and ply sheets in the affected area. |
| The vapor retarder extends
continuously throughout the deck plane. |
Install vapor retarder
to incomplete or noncontinuous areas. |
| End laps, side laps, openings,
and penetrations are sealed. |
Install additional Fields
asphalt and ply sheets to ensure adequate seals. |
| Vapor retarder is sealed
at the perimeter and flashings. |
Seal vapor retarder at
perimeter and flashings per the "Roof Flashing Details"
section. |
| Vapor retarders are correctly
tied into other intersecting vapor retarders. |
Install additional sheets
to ensure adequate vapor retarder tie-ins and correct installations. |
| Criteria |
Corrective
Action |
| Insulation is protected
before, during, and after installation. |
Protect insulation. Remove
damaged or wet installation from the project site. |
| Insulation boards are
installed at the correct angle to the deck's pitch. |
Reinstall insulation boards
to the correct angle of the deck's pitch. |
| The planes of finished
surfaces of adjacent insulation boards are vertically offset less
than 1/4". |
Vertical offset of insulation
board surface plane shall be corrected by shaving the insulation boards,
filling, leveling the gap with compatible material, or adding tapered
insulation. |
| Only the quantity of insulation
is installed that can be covered with the completed roof system membrane
through the reflective surfacing or a glaze coating in the same day. |
Cover all insulation the
same day installed with the roof system membrane. Remove any damaged
insulation from the project site. |
| The hot asphalt adhesive
is being applied at the uniform rate of 30 lbs per 100 sq ft; or the
ambient asphalt adhesive is being applied at the uniform rate of 4
gals per 100 sq ft. The insulation is being embedded into the asphalt
while it is still fluid. |
Remove faulty adhered
insulation and replace with correctly adhered insulation. |
| Mechanically fastened
insulation has the quantity and correct placement of fasteners as
specified |
Install additional fasteners
as specified and space correctly. |
| Water cutoffs are installed
at the end of each day at the edge of the roof system so as to keep
water from entering the system. The water cutoffs are removed prior
to resuming the installation. |
Install water cutoffs
at the end of each day. Remove damaged insulation from the project
site and replace. |
| All insulation joints
are staggered per each layer and between layers. |
Remove nonstaggered insulation
boards and adjust boards to achieve correct stagger. |
| Insulation boards are
in moderate contact. Occasional gaps between boards are less than
1/4" and are not continuous for more than the length of one insulation
board. |
Insulation gaps in excess
of 1/4" shall be filled with the correct insulation board or
compatible material. |
| Insulation boards are
reasonably square. |
Out of square insulation
boards creating gaps in excess of 1/4" are prohibited. The insulation
manufacturer shall be requested to take corrective action for out
of square boards. |